Engineering Guide

Cable Tray Selection Guide

Material, finish, fill ratio and support spacing — the four decisions behind every cable tray specification.

1. Choose material & finish by environment

The finish decides the service life of the tray, not the steel grade alone. Our standard options follow the factory catalogue: EZ (post-fabrication electro-zinc, ISO 20-81/NF EN 12-329/DIN 50961) for ordinary indoor work; GS (continuous electro-zinc, NF EN 10-327/DIN 50976) for higher-demand indoor areas; GC (hot-dip galvanized, NF/EN/ISO 1461) for outdoor; DC (dacromet zinc-aluminum coating) where thin coatings with high corrosion resistance are required; and 316 electropolished for chemically aggressive zones such as chemical, food and offshore plants.

EnvironmentRecommended material / finish
Dry indoor ceilingsPre-galvanized (DX51D+Z) or powder coated steel
Outdoor / general industrialHot-dip galvanized steel (GC, NF/EN/ISO 1461)
Humid / coastal sitesZinc-aluminum-magnesium steel, zinc layer up to 275 g/m² (19–20 μm)
Marine, offshore, high-corrosionStainless 304 / 316 electropolished, or FRP
Food & pharma washdown areas304 stainless, electropolished finish

2. Fill ratio: how much cable a tray may carry

Fill ratio is the share of the tray cross-section occupied by cable. Overfilled trays trap heat and fail inspection. The figures below are the ones we apply when checking customer cable schedules:

Cable typeFill ratio
Power & control cable (trough / perforated)≤ 40%
PV DC cable — national standard limit≤ 40%
PV DC cable — high-temperature best practice≤ 30%, plus 20% margin reserved
Data / fiber in open mesh trayHigher fill acceptable — open structure aids heat dissipation

3. Support spacing and installation

  • Brackets fixed with expansion bolts at 1.5–3 m spacing, selected by section and load
  • Allowable load drops sharply beyond the rated span — deflection grows with the cube of span; ask for tested deflection data before hanging 2 m-rated tray at 3 m
  • Splice plates and bonding strips keep electrical continuity across joints
  • Standard straight length 3000 mm; order widths in 50 mm steps, lengths in 100 mm steps; special sizes custom-made

4. Grounding and accessories

Copper grounding bolts are standard accessories on every run — order them with the tray, not as an afterthought. Complete the system with T, cross and riser fittings, splice plates, covers and dividers; mesh systems use tool-free snap-on accessories (CRP brackets, ED connectors, KITASSTR clamps) that cut installation time substantially.

Send your cable schedule for a fill-ratio check & quote