Cable Tray Selection Guide
Material, finish, fill ratio and support spacing — the four decisions behind every cable tray specification.
1. Choose material & finish by environment
The finish decides the service life of the tray, not the steel grade alone. Our standard options follow the factory catalogue: EZ (post-fabrication electro-zinc, ISO 20-81/NF EN 12-329/DIN 50961) for ordinary indoor work; GS (continuous electro-zinc, NF EN 10-327/DIN 50976) for higher-demand indoor areas; GC (hot-dip galvanized, NF/EN/ISO 1461) for outdoor; DC (dacromet zinc-aluminum coating) where thin coatings with high corrosion resistance are required; and 316 electropolished for chemically aggressive zones such as chemical, food and offshore plants.
| Environment | Recommended material / finish |
|---|---|
| Dry indoor ceilings | Pre-galvanized (DX51D+Z) or powder coated steel |
| Outdoor / general industrial | Hot-dip galvanized steel (GC, NF/EN/ISO 1461) |
| Humid / coastal sites | Zinc-aluminum-magnesium steel, zinc layer up to 275 g/m² (19–20 μm) |
| Marine, offshore, high-corrosion | Stainless 304 / 316 electropolished, or FRP |
| Food & pharma washdown areas | 304 stainless, electropolished finish |
2. Fill ratio: how much cable a tray may carry
Fill ratio is the share of the tray cross-section occupied by cable. Overfilled trays trap heat and fail inspection. The figures below are the ones we apply when checking customer cable schedules:
| Cable type | Fill ratio |
|---|---|
| Power & control cable (trough / perforated) | ≤ 40% |
| PV DC cable — national standard limit | ≤ 40% |
| PV DC cable — high-temperature best practice | ≤ 30%, plus 20% margin reserved |
| Data / fiber in open mesh tray | Higher fill acceptable — open structure aids heat dissipation |
3. Support spacing and installation- Brackets fixed with expansion bolts at 1.5–3 m spacing, selected by section and load
- Allowable load drops sharply beyond the rated span — deflection grows with the cube of span; ask for tested deflection data before hanging 2 m-rated tray at 3 m
- Splice plates and bonding strips keep electrical continuity across joints
- Standard straight length 3000 mm; order widths in 50 mm steps, lengths in 100 mm steps; special sizes custom-made
4. Grounding and accessories
Copper grounding bolts are standard accessories on every run — order them with the tray, not as an afterthought. Complete the system with T, cross and riser fittings, splice plates, covers and dividers; mesh systems use tool-free snap-on accessories (CRP brackets, ED connectors, KITASSTR clamps) that cut installation time substantially.